Input
|
Phase
Rated Voltage
Voltage Range
Frequency Range
Power Factor
Current THDi
Bypass Voltage Range
ECO Range
Hamonic Current
|
Single phase & Ground
220/230VAC +/- 25%
140-290V*
40Hz-70Hz (settable) +/- 0.1%
>0.99
5% at 100% non-linear load
Max, voltage; +5% (optional +5%, +10%, +25%)
Min. voltage:-45% (oplional -20%,-30%, -45%)
Frequency protection range: +/-10%
same as the bypass
<5% ( 100% non-linear load )
|
Output
|
Phase
Rated Voltage
Power Factor
?Voltage Regulation
Frequency - Utility Mode
- Battery Mode
Crest Factor
THD
Wave Form
|
Single phase & Ground
220/230VAC
0.9
?+/- 1%
1%,2%,4%,5%,10% of the rated frequency (optional)
50Hz +/- 0.1% Hz
3:1
< 2% with Linear Load
< 5% with non Linear Load
Pure Sine Wave
|
Efficiency
|
AC Mode (full load)
Battery Mode (full load)
ECO Mode (tull load)
|
Up to 90%
>88%
?>94%
|
Battery
|
Voltage
Capacity (Standard unit)
Backup Time
Recharge Time to 90%
Charging Current -Standard
Battery Number
Battery Socket
|
192/216/240 Vdc
12V/9Ah
15-30 min (Depend on load), Estimated remaining time display on the LCD
4-6 Hours
1A (S), 6A (H)
16/18/20 pcs (Settable)
Anderson Like PowerPole Modular Connectors
|
Transfer Time
|
|
Utility to Battery; 0ms, Utility to Bypass <4ms
|
Protection
|
Overload - AC Mode
- Batt. Mode
- Bypass Mode
Short Circuit
Overheat
Battery Low
Self-Diagnostics
EPO
Battery
Noise Suppression
|
108%+/-5% 150%+/-5% 108%+/-5% 150%+/-5% Load <100%-150%; 30S; Load >150%; 300ms then shutdown UPS completely
Load >130%; 60S then shutdown output
Hold Whole System
Line mode; Switch to Bypass; Battery Mode, shutdown UPS immediately
Alarm and Switch off
Upon Power On and Software Control
Shutdown UPS immediately
Advanced Battery Management
Compiles with EN962040-2
|
ALARM
|
Audible & Visual
|
Line Failure, Battery Low, Overload, System Fault
|
Display
|
Status LED & LCD
Reading on the LCD
|
Load/Battery/Input/Output/Operating Mode information
Load/Battery/Input/Output/Operating Mode information
|
Physical
|
Dimension(WxHxD) mm
Weight (kg)
Input Connection
Output Connection
External Battery Connection
|
250 x 655 x 590
70kg
hardwired
hardwired
Anderson like PowerPole Modular connectors
|
Communication
Interface
|
Smart RS232/USB Port
Communication Slot
R.J45
|
Support Windows Family, Linux, FreeDSB, etc.
SNMP Card (independent to RS232)
Built-in Power Surge, Lightning Protection Device
|
Environment
|
??Operating Temperature
Storage Temperature
Humidity
Altitude
Noise
|
0 °C - 40 ° C
-25 °C - 55 °C
0-95% (Non-condensing)
<1500 m. (derating while > 1500m)
<55 dB (at 1 meter)
|
?Safety Conformance
|
|
CE
|
Industry Standard
|
Safety
EMI
EMS
Surge
ISO
|
??Meet IEC62040-1 GB4943
IEC 62040-2
IEC 62040-2
Meeting IEC62040-1 1.2/50uS-8/20uS 6kV/3kA
9001 : 2015 , 14001 : 2015
|